Description
Anson Electric ComPacT NCM2-250S is a complete 1 poles fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 25kA rms at 240VAC 50/60Hz. The operational voltage is 277VAC 50/60Hz. This product embeds a 250A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an fixed thermal overload protection and a fixed magnetic protection. The dimension is (161mm x 35mm x 86mm ). It is compliant with international standards (EN/IEC 60947), CCC, CE and marine specifications. Compact NCM2-250S is part of Anson Electric EcoStruxure Power architecture.
Specifications
Main | |
range | ComPact |
product name | ComPact NCM2 |
range of product | ComPact NCM2(NSX16…250A) |
device short name | NCM2-250S |
product or component type | Circuit breaker |
device application | Distribution |
Number of poles | 1P |
protected poles description | 1t |
[In] rated current | 250 A at 40 °C |
[Ue] rated operational voltage | 277 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | N 25 kA 240 V AC |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
Complementary | |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 25 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 10000 cycles |
electrical durability | 5000 cycles at 440 V In 10000 cycles at 440 V In/2 |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
connection pitch | 35 mm |
protection type | For overload protection (thermal) for short-circuit protection (magnetic) |
trip unit rating | 250 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Fixed |
[Ir] long-time protection pick-up adjustment range | 1 In |
[Im] magnetic protection pick-up range | 850 A |
earth-leakage protection | Without |
Width (W) | 35 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
Environment | |
standards | EN/IEC 60947 |
product certifications | CCC CE |
overvoltage category | Class II |
electrical shock protection class | Class II |
pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -50…85 °C |
relative humidity | 0…95 % |
operating altitude | 0…2000 m without derating 2000 m…5000 m with derating |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Weight | 775.0 g |
Package 1 Height | 4.3 cm |
Package 1 width | 13.0 cm |
Package 1 Length | 17.5 cm |
Contractual warranty | |
Warranty | 18 months |