ASQ-125F3 Isolating Switch

asq-125f3ASQ-125F4 Isolating Switch

Product Description
ASQ-125 Series Load Isolating Switch (hereinafter referred to as the switch) is developed with introduced European advanced technology by our company.
With international advanced level, it is an ideally upgraded product among similar products in domestic market.
The switch is widely used in construction, power, petrochemical, distribution and automation systems of other industries.
With modular designed structure, flexible and varied comparability, glass fiber reinforced unsaturated engineering plastic manufactured outer case, the switch
has a high dielectric property, protection ability and reliable operation safety.
Operating mechanism is the spring energy storage, instantaneous release of the acceleration mechanism, instantaneous on and break the double break point
contact structure. With a variety of structure and operation mode, the switch has nothing to do with the speed of operating handle. The switch has a window for
direct observation of the broken state of contact. It can be operated from inside, outside and behind the cabinet, or from front and side. The switch has a back
panel connection.
The switch has the advantages of beautiful appearance, novel, simple, small size and complete function. It is an ideal choice for the similar products.

Main technical Parameter

Switch modelAASQ40FASQ63FASQ80FASQ100FASQ125F
Rated insulation voltage and rated working voltage

Dielectric strength

Rated impulse withstand voltage

AC-20/DC-20 50 Hz 1min.V750750750750750
kV66666
Kv88888
Rated heating current and rated operating current

Minimum cross-sectional area of conductor

AC-20/DC-2040℃)3)
A406380115125
40℃)3)A406380115125
60℃)3)A32506380100
Cumm21016253550
Rated operting currentAC-21A415VA406380100125
440~690VA406380100125
AC-22A415VA406380100125
440~500VA406380100125
690VA406380100125
AC-23A415VA2363758090
440VA2363656578
500VA2345586070
690VA1220204050
Rated operting current/Inter electrode seriesDC-21A24~48V1)A32/163/180/1100/1125/1
110VA32/263/280/2100/2125/2
220VA32/363/480/4100/4125/4
440VA16/416/416/4
500VA16/416/416/4
750VA32/8
DC-22A24~48V1)A32/163/180/1100/1125/1
110VA32/263/280/2100/2125/2
220VA32/445/445/463/480/4
440VA10/410/410/4
750VA25/8
DC-23A24~48V1)A32/163/180/1100/1125/1
110VA32/263/280/2100/2125/2
220VA32/445/445/463/463/4
440VA10/410/410/4
750VA16/8
Rated power
(These values are for reference only, and may vary from different motor manufacture)
AC-23A220~240VkW5.511222222
400~415VkW1122373745
440VkW1122373745
500VkW1122373745
690VkW111518.53745
Rated breaking capacityAC-23A至415VA184360640640720
440VA184360448520624
500VA184360464480560
690VA96160160320400
Rated breaking capacity/Inter electrode seriesDC-23A24~48VA128/1180/1252/1400/1500/1
110VA128/2180/2252/2400/2500/2
220VA128/4180/4180/4252/4252/4
440VA40/440/440/4
750VA64/8
Rated short circuit current Ip(R.M.S.)
And the curresponding maximum cut off current ic

Refer cut offcurrent to the numberical value offered by fuse manufacturer
Single phase test based on IEC 60269

Ip (R.M.S.)50kAkA16.516.5
≤415VA125/125125/125
100kAkA
≤500VA
10kAkA8.28.2
≤690VA125/10125/10
50kAkA1010
≤690VA63/6363/63
Rated ICW(R.M.S.) Icw690V, 0.25skA
690V, 1skA2.52.5
Rated short circuit switching capacity Icm690V/500VkA3.63.6
Rated capacitor capacity (rated value of the capacitor subject to fuse limit)400~415VkVAr4050
Function loss/poleW46.3
Mechanical lifeOper2000020000
Weight(without attachment)3Pkg0.360.36
4Pkg0.50.5
Cable specificationsmm210-7010-70
AWG8-1008-100
Terminal tightening torque

Operating torque

Nm66
3PNm22

1) Below 48V, OT80 is recommended to be used in parallel, especially in a polluted environment.

2) 200A, the minimum cable specifiction 95mm2, use OZXT2 or bus connections.

3) IEC 60947-1,§ 6.1.1 standard

Overall and Mounting Dimensions

qq%e6%88%aa%e5%9b%be20161226103924

Fill out my online form.