ACX2-95 Magnetic Starter
Application
ACX2 series magnetic starter is suitable for staring 3-phase squirrel-cage motor in the circuit of AC 50/60Hz,rated insulation voltage 690V, under AC-3 utilization category, rated operational voltage 380V, rated operational current range from 9A to 95A. The magnetic starter with thermal overload relay are protect AC 3-phase motor against overland and phase losing.
Normal Running And Installation Conditions
- Ambient air temperature: -5℃~+40℃, the average value should not exceed +35℃ within 24 hours.
- Elevation: at most 2000m.
- Atmospheric conditions: When the temperature at 40℃, the relative humidity of atmosphere should be at the most 50%. When at relatively low temperatures, it could have higher relative humidity. Monthly maximum relative humidity could be not more than 90%. Special measures should be taken due to occurrence of dews.
- Class of pollution: Class 3
- Installation category: III
- Installation conditions: Degree of inclination between fitting surface and vertical surface should not exceed ±5°.
- Impact shock: Product should be installed and used in the place where often shakes and impacts.
Type of Construction
Magnetic starter has a case with protection category IP65, JRS4 thermal overload relay connect with terminals through three wires, and fix together with ACC1 contactor. There are two buttons on the case, green one is “turn on”, red one is “turn off” or “reset”.
Main technical Parameter
Model | Rated operational current(A) 380V | Conventional heating current(A) | Power of controllable 3-phase squirrel-cage motor(kW) AC-3 | Average power consumption VA (20℃) 50Hz | Unit weight(kg) | ||||
AC3 | AC4 | 220V | 380V | 660V | Pick-up | Holding | |||
ACX2-09 | 09 | 3.5 | 20 | 2.2 | 4 | 5.5 | 76 | 9.4 | 0.9 |
ACX2-12 | 12 | 5 | 20 | 3 | 5.5 | 7.5 | 76 | 9.4 | 0.9 |
ACX2-18 | 18 | 7.7 | 32 | 4 | 7.5 | 10 | 76 | 9.4 | 0.92 |
ACX2-25 | 25 | 8.5 | 40 | 5.5 | 11 | 15 | 110 | 11 | 1.3 |
ACX2-32 | 32 | 12 | 50 | 7.5 | 15 | 18.5 | 110 | 11 | 1.33 |
ACX2-40 | 40 | 18.5 | 60 | 11 | 18.5 | 30 | 230 | 32 | 3.65 |
ACX2-50 | 50 | 24 | 80 | 15 | 22 | 33 | 230 | 32 | 3.65 |
ACX2-65 | 65 | 28 | 80 | 18.5 | 30 | 37 | 230 | 32 | 3.65 |
ACX2-80 | 80 | 37 | 110 | 22 | 37 | 45 | 230 | 32 | 3.8 |
ACX2-95 | 95 | 44 | 110 | 25 | 45 | 55 | 230 | 32 | 3.8 |
Overall and Mounting Dimensions
Wiring Scheme
…