ACF1-12 AC contactor

acf1-12ACF1-12 AC contactor

Application

ACF1 series AC contactors are suitable for frequency 50/60Hz, rated insulation voltage up to 1000V,rated operation current 9~475A under AC-3 duty. It is mainly used for making/breaking electric circuit at a long distance & for frequent starting/stopping & with thermal relay to compose a magnetic motor starter. The product conforms to IEC60947-4-1 standard.

 

 

 

 

 

 

Specification

TypeACF1-09
ACF1-12
ACF1-16
ACF1-22
ACF1-32ACF1-45
ACF1-63
ACF1-75
ACF1-85
ACF1-110
ACF1-140
ACF1-170
ACF1-205
ACF1-250
ACF1-300
ACF1-400
ACF1-475
Mechanical endurance(x106)101010888888
Conventional thermal current(A)20304580100160210300400/550
Rated insulation voltage(V)660660660100010001000100010001000
Rated(380V)operating current(A)AC-39/1216/223245/6375/85110/140170/205250/300400/475
AC-43.3/4.37.7/8.515.624/2834/4254/6875/96110/125150
Power of controllable motor(kW)AC-4380V4/5.57.5/111522/3037/4555/7590/110132/160200/250
660V5.5/7.5113239/5567100156235375
Power of controllable motor(kW)AC-4380V1.4/1.93.5/47.512/1417/2127/3538/5058/6681
660V2.4/3.36/6.61320.8/2429.5/3646.9/6066/86100/114140
Frequency of operation(l/H)AC-310007507501200/10001000/8501000/750700/500700/500500/420
AC-4250250250400/300300/200300/200200/130200/130150
Electrical endurance(x106)AC-31.21.21.21.21.21.21.21.21.2
AC-40.20.20.20.20.20.20.20.20.2
Operating voltage range of coil(0.8~1.1)Ue
Power consumptionAtracting(VA)101012.11732395884115
Starting(VA)686910118333055091014602450
Ratedinsulation voltage of auxitiary contacts(V)690690690690690690690690690
Conventional thermal current of auxitiary contacts101010101010101010
Rated operating current of auxitiary cpntacts(A)AC15
380/220
6/106/104/64/64/64/64/64/64/6
DC13
220V
0.450.450.480.480.480.480.480.480.48
Rated voltage of the control coil(V)50Hz24,36,48,110,127,220,380,etc.
60Hz24,110,220,440,etc.

Outline and Mounting Dimension