ComPacT NCM2-16/250 4 pole Earth-leakage add-on protection module VigiPacT, 440VAC to 550VAC, 30mA to 30A,

Description

Anson electric is a Vigi add-on module for ComPact NCM2-63/250 that provides an earth-leakage protection. It is used for 4 poles circuit breakers.

The operational rated voltage is between 440 and 550 VAC 50/60 Hz.

The earth-leakage sensitivity is adjustable from 30 mA to 30 A. It is installed directly on the device terminals and directly actuates the trip unit in case of earth-leakage default.

This Vigi add-on module is self-powered internally by the distribution-system voltage, even is supplied by only 2 phases. It is compliant with IEC 60947-2 standard, annex B.

 

 

 

 

Specifications

Main
range of product ComPact NCM2(NSX16…250)
device short name VigiPacT
product or component type Vigi add-on
device application Wiring
range compatibility ComPact NCM2(NSX16…250 circuit breaker)
poles description 4P
[In] rated current 16A…250 A
earth-leakage protection class Class A
Class AC
residual earth-leakage sensitity adjustment type Adjustable
earth-leakage sensitivity 0.03 A for class A
0.1 A for class A
0.3 A for class A
0.5 A for class A
1 A for class A
3 A for class A
10 A for class AC
30 A for class AC
residual earth-leakage time delay adjustment type Adjustable
[Δt] residual earth-leakage time delay adjustment 0 ms
60 ms
150 ms
300 ms
500 ms
800 ms
1.2 s
4 s
Complementary
network type AC
network frequency 50/60 Hz
[Ue] rated operational voltage 440…550 V AC 50/60 Hz conforming to IEC 60947-2
earth-leakage protection With
maximum breaking time 800 ms
overvoltage category IV
Environment
electrical shock protection class Class II
standards IEC 60947-2
Fill out my online form.