circuit breaker EasyPact NZC125H – TMD – 80 A – 1 pole

Description:

Anson Electric EasyPact NZC100H is a 1 pole fixed circuit breaker designed for the protection of low voltage electrical installations. It is used for standard applications in industries and buildings, offering good performance at competitive price The breaking capacity (Icu) is 25kA rms at 240VAC 50/60Hz. The operational voltage is 415VAC 50/60Hz. The rating of the thermal-magnetic trip unit is 80A. The trip unit provides fixed overload and instantaneous protections. The dimensions for this 1 pole version are 25mm (W) x 130mm (H) x 60mm (D). Easypact EZC100H is compliant with international standards (IEC 60947) and marine certifications.

 

 

 

 

 

Specifications:

Main
range of product Easy Pact
product or component type Circuit breaker
device short name Easypact NZC100H
circuit breaker name Easypact NZC100H
device application Distribution
poles description 1P
protected poles description 1t
network type AC
network frequency 50/60 Hz
[In] rated current 80 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 125 V DC conforming to IEC 60947-2
415 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity code H
breaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 5 kA at 125 V DC conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation Yes conforming to IEC 60947-2
utilisation category Category A
trip unit name TM-D
trip unit technology Thermal-magnetic
trip unit rating 80 A at 50 °C
protection type Short-circuit protection
Overload protection
pollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1

 

Complementary
control type Toggle
mounting mode Fixed
mounting support Backplate
upside connection Front
downside connection Front
mechanical durability 8500 cycles
electrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
connection pitch 25 mm
local signalling Positive contact indication
neutral protection setting Without protection
earth-leakage protection Without
height 130 mm
width 25 mm
depth 60 mm

 

Environment
standards EN/IEC 60947-2
JIS C8201-2-2
GB/T 14048.2
EN/IEC 60947-1
IP degree of protection IP20 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
ambient air temperature for operation -25…70 °C
ambient air temperature for storage -35…85 °C

 

 

Contractual warranty
Warranty 18 months

 

 …

Fill out my online form.