ACC1-D18 contactor 3 pole 18A, 230V AC 50/60Hz

Description

Anson Electric ACC1-D contactor, 3 poles (3NO), for motor control applications up to 18A/690V AC-3/3e (7.5kW@400V).

It provides a 110V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals.

For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability.

Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

 

 

 

 

Specifications

Main
range ACC1 Deca
product or component type Contactor
device short name ACC1-D18
contactor application Resistive load
Motor control
utilisation category AC-1
AC-3
AC-3e
poles description 3P
[Ue] rated operational voltage Power circuit: <= 690 V AC 25…400 Hz
[Ie] rated operational current 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 110 V AC 50/60 Hz
Complementary
motor power kW 10 kW at 500 V AC 50/60 Hz
10 kW at 660…690 V AC 50/60 Hz
4 kW at 220…230 V AC 50/60 Hz
7.5 kW at 380…400 V AC 50/60 Hz
9 kW at 415…440 V AC 50/60 Hz
pole contact composition 3 NO
protective cover With
auxiliary contact composition 1 NO + 1 NC
[Ui] rated insulation voltage Control circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
overvoltage category III
[Ith] conventional free air thermal current 10 A (at 60 °C) for control circuit
32 A (at 60 °C) for power circuit
Irms rated making capacity 140 A AC for control circuit conforming to IEC 60947-5-1
300 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity 300 kA at 440 V for power circuit conforming to IEC 60947
associated fuse rating 10 A gG for control circuit conforming to IEC 60947-5-1
35 A at <= 690 V coordination type 2 for power circuit
50 A at <= 690 V coordination type 1 for power circuit
control circuit type AC at 50/60 Hz
coil technology Without built-in bidirectional peak limiting diode suppressor
average impedance 2.5 mOhm – Ith 32 A 50 Hz for power circuit
power dissipation per pole 0.8 W AC-3
2.5 W AC-1
0.8 W AC-3e
minimum switching current 5 mA for control circuit
minimum switching voltage 17 V for control circuit
non-overlap time 1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts
operating time 4…19 ms opening
12…22 ms closing
maximum operating rate 3600 cyc/h 60 °C
inrush power in VA 70 VA cos phi 0.75 (at 20 °C)
hold-in power consumption in VA 7 VA 50/60 Hz cos phi 0.3 (at 20 °C)
heat dissipation 2…3 W at 50/60 Hz for control circuit
insulation resistance > 10 MOhm for control circuit
tightening torque Control circuit: 1.7 N.m – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – with screwdriver Philips No 2
Power circuit: 1.7 N.m – with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m – with screwdriver Philips No 2
Control circuit: 1.7 N.m – with screwdriver pozidriv No 2
Power circuit: 1.7 N.m – with screwdriver pozidriv No 2
mounting support Rail
Plate
mechanical durability 15000000 cycles
safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
operating altitude 3000 m without derating
compatibility code ACC1-D18(LC1D)
standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
product certifications CCC
Environment
IP degree of protection IP2x conforming to IEC 60529
climatic withstand conforming to IEC 60947-1 Annex Q category D
permissible ambient air temperature around the device -40…70 °C at Uc
ambient air temperature for storage -60…80 °C
fire resistance 850 °C conforming to IEC 60695-2-1
Contractual warranty
Warranty 18 months
Fill out my online form.