Description
Anson electric is a Vigi add-on module for ComPact NCM2-400/630 that provides an earth-leakage protection. It is used for 4 poles circuit breakers.
The operational rated voltage is between 440 and 550 VAC 50/60 Hz.
The earth-leakage sensitivity is adjustable from 30 mA to 30 A. It is installed directly on the device terminals and directly actuates the trip unit in case of earth-leakage default.
This Vigi add-on module is self-powered internally by the distribution-system voltage, even is supplied by only 2 phases. It is compliant with IEC 60947-2 standard, annex B.
Specifications
| Main | |
| range of product | ComPact NCM2(NSX400…630) |
| device short name | VigiPacT |
| product or component type | Vigi add-on |
| device application | Wiring |
| range compatibility | ComPact NCM2(NSX400…630 circuit breaker) |
| poles description | 4P |
| [In] rated current | 400A…630 A |
| earth-leakage protection class | Class A Class AC |
| residual earth-leakage sensitity adjustment type | Adjustable |
| earth-leakage sensitivity | 0.03 A for class A 0.1 A for class A 0.3 A for class A 0.5 A for class A 1 A for class A 3 A for class A 10 A for class AC 30 A for class AC |
| residual earth-leakage time delay adjustment type | Adjustable |
| [Δt] residual earth-leakage time delay adjustment | 0 ms 60 ms 150 ms 300 ms 500 ms 800 ms 1.2 s 4 s |
| Complementary | |
| network type | AC |
| network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 440…550 V AC 50/60 Hz conforming to IEC 60947-2 |
| earth-leakage protection | With |
| maximum breaking time | 800 ms |
| overvoltage category | IV |
| Environment | |
| electrical shock protection class | Class II |
| standards | IEC 60947-2 |