NFPV-32 20A 1000v Solar photovoltaic fuse
Application
NFPV-32 Fuse was designed and manufactured , complying with the standard IEC60269-6 The Rated Current up to 30A,rated voltage up to 1000V DC. It applied for PV DC combiner box, inverter etc, with the main function of over-current protection and effective disconnection.
A range of 10×38mm fuse links specifically designed for protecting photovoltaic strings. These fuse links are capable of interrupting low overcurrents associated with faulted photovoltaic string arrays(reverse current, multi-array fault).
Parmeter
| NFPV-32 20A Fuse | ||
| Pole | 1P | |
| According to | IEC 60269-6 | |
| Electrical Characteristics | ||
| Rated Working Voltage | Ue | 1000V DC |
| Rated Current | In | 20 A |
| Breaking Capacity | 33KA | |
| Max Power Dissipation | 3W | |
| Contol and Indication | ||
| Operating State/Fault Indication | Indicator Light OFF/Indicator Light ON | |
| Connection and Installation | ||
| Wire | 2.5mm2~25 | |
| Terminal Screws | M5 | |
| Torque | Nm | 2.5 |
| Degree of Protection | IP20 | |
| Installation Environment | ||
| Fuse Size | 10×38 mm | |
| Operating Temperature Range | TU | -30℃~+70℃ |
| For Mounting On | TH35-7.5/DIN35 | |
| Pollution Degree | 3 | |
| Relative Humidity | +20 ℃≤ 95%,+40℃≤50% | |
| Weight | 0.07kg Per pole | |
| Installation Class | Ⅲ | |
Dimensions
…

English
简体中文
RU
PT