NL1-25B 3P Surge Protection Device
Integral housing combined lightning current and surge arrester for protecting three-phase TT and TN-S systems (“3+1” circuit)against surges.
- Coordinated spark-gap-based lightning current and surge arrester
- Maximum systems availability due to RADAX Flow follow current limitation
- Capable of protecting terminal equipment
Technical data | |
Type | NL1-25B-275/3 |
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (< 5m) | type 1 + type 2 |
Nominal a.c. voltage (Un) | 230 / 400 V AC (50/60 Hz) |
Max. continuous operating a.c. voltage (Uc) | 275 V AC (50/60 Hz) |
Lightning impulse current (10/350μs) [L1+L2+L3+N-PE] (Itotal) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2,5 MJ/ohms |
Lightning impulse current (10/350μs) [L, N-PE] (Iimp) | 25 kA |
Specific energy [L, N-PE] (W/R) | 156,25 kJ/ohms |
Nominal discharge current (8/20μs) [L, N-PE]/[L1+L2+L3+N-PE](In) | 25 kA / 100 kA |
Voltage protection level [L-PE]/[N-PE] (Up) | 1,5 kV / 1,5 kV |
Follow current extinguishing capability a.c. (Ifi) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gL/gG fuse up to 50 kArms(prosp.) |
Response time (tA) | < 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gL/gG |
Max. backup fuse (L-L’) | 125 A gL/gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 530 V / 120 min. – withstand |
Range of operating temperatures [parallel] / [series] (TU) | -40…+80°C / -40…+60°C |
Operating state / fault indication | – |
Number of ports | 1 |
Cross-sectional area (L1, L1′,L2, L2′, L3, L3′, N, N’, PE, PE’) (min.) | 10 mm2 solid /flexible |
Cross-sectional area (L1, L2, L3, N, PE ) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1′, L2′, L3′, N’, PE’) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rail acc. to EN 60715 |
Enclosure material | thermoplastic |
Place of installation | indoor installation |
Degree of protection | IP20 |
Capacity | 8 module(s), DIN 43880 |
Approvals | CE |